11
WALL SLEEVE INSTALLATION
FRAMING FOR WALL SLEEVE (WS900B)
When installed in opening, the Wall
Sleeve must be horizontally level (side-
to-side) and pitched 1/4 bubble to the
outside. (
NOTE: To ensure unit’s
maximum efficiency, DO NOT
over- or under-pitch.)
2" MIN
WOOD SCREW
TOGGLE BOLT
EXPANSION
ANCHOR BOLT
SCREWS
PLASTIC
ANCHOR
MOUNTING HOLES
(drilled by Installer)
NO HOLES
PERMITTED IN
BOTTOM OF CASE
(EXCEPTION -- INTERNAL
DRAIN KIT)
FASTENING WALL SLEEVE
INSTALLATION NOTES
(1). If Subbase (PTSB***C) is installed, allow minimum 3-1/4” height clearance and maximum 5” height
clearance between wall sleeve and floor; allow minimum 2-3/4” protrusion from wall to front of
wall sleeve.
(2). Drain Kit (DK9001) shipped separately. Can be mounted either right side, left side, or bottom of
sleeve. If mounted to bottom of sleeve, allow 2” height clearance from floor to bottom of sleeve.
(3). For U.L. approval -- 265v units must use Amana Subbase (PTSB***C) or Amana Hard Wire Kit
(PTPWHWK4). Over-current protection on 265V units must be by cartridge style time delay fuses
which are included and factory installed on Amana chassis.
(4). If Hydronic Kit (HWK03 or HVK03) is installed, Wall Sleeve must extend exactly 3 inches into the
room from finished interior wall.
FINISHED FLOOR
42 1/4"
16 1/4"
MIN
MAIN STUD
JACK STUDS
HEADER - 4" x 4" OR
DOUBLE 2"x 4" ON EDGE
SUB-FLOOR
CRIPPLE
JACK STUD
ADJUST FRAMING TO
SECURE THIS DIMENSION